The following topics were discussed (agreements in red):

 

1.) Issue on

RegulatingControl.targetValue and mode

OperationalLimit.value

               

proposal: Should be moved out of the EQ set

ENTSO-E IOP Call – 20 Feb 2012:  It is OK for IOP participants

 

2) ExternalNetwork issue

Why is this defined as a subtype of RegulatingCondEq? – ENTSO-E IOP Call – 20 Feb 2012:  Because connection to a external grid that can have slack node (in most of the cases the ExternalNetwork is the slack); ExternalNetwork stands on its own – not part of reduction of a portion of a grid.

Was originally modeled as EquivalentInjection.  Why was this changed? ENTSO-E IOP Call – 20 Feb 2012:  EquivalentInjection is coming from grid reduction; this is not the same for ExternalNetwork

Attribute voltageFactor is of type PU.  Why was this necessary?  Could this be changed to PerCent?  This needs to be clearly explained in the description. ENTSO-E IOP Call – 20 Feb 2012:  We need to check the description and IEC 60909

Agreed to add the attributes from ExternalNetwork to EquivalentInjection. ENTSO-E IOP Call – 20 Feb 2012:  IOP participants insist to have the ExternalNetwork as a separate class as initially suggested

Do we need to add Short Circuit specific attributes for minP and maxP?  We assume that an extra set is not necessary. ENTSO-E IOP Call – 20 Feb 2012:  – If we have separate classes we don’t have this issue

 

3) Additional attributes to AsynchronousMachine

Attribute nominalFrequency needs more description. ENTSO-E IOP Call – 20 Feb 2012:  Nameplate data gives info if the machine is 50/60 Hz

Attribute nominalSpeed needs more description. ENTSO-E IOP Call – 20 Feb 2012:  Nameplate data. Depends on the slip and number of pole pairs.

Is “ratedP” the best name for mechanical power?  Would ratedMechanicalPower be better? ENTSO-E IOP Call – 20 Feb 2012:  OK  Should this be ActivePower? ENTSO-E IOP Call – 20 Feb 2012:  OK - Watts

Description of “reversible” needs to be expanded. ENTSO-E IOP Call – 20 Feb 2012:  To be checked in IEC60909

 


The updated presentation for the meeting is available here. (IOP agreements are shown in green in the slides)

These issues were sent to WG13 and a common call was suggested (either on 27 Feb-in IOP time or on 29 Feb- in WG13 time slot)

Participants:
1 Zhu, Jun 
2 Milin, Emilie 
3 Parma, Ferdinando 
4 Schmid, Christoph 
5 Stanescu, Oana 
6 Mariański, Krzyszt… 
7 Lopez, Rafael 
8 Pantea, Stefan 
9 Zivkovic, Nemanja 
10 Svoboda, Petr 
11 Akel, Youssef 
12 Cott, Giatgen 
13 Olsen, Svein 
14 Rogowski, tomasz 
15 Bozukov, Georgi 
16 Merckx, Christian 
17 Tomic, Dragan 
18 Martinovic, Lajos 
19 McMorran, Alan 
20 Waight, Jim 
Members Supporting CIM