Notes IOP Call - 14 May 2012
Agenda:
1) Review of IOP poll
Only 8 vendors completed doodle link. Most of the vendors will test import/export only. We need at least a few vendors to test load flow and dynamics simulations in order to test the profile in full.
For the time being only CESI volunteers to work on ENTSO-E 16 nodes model and to convert and adapt it to ENTSO-E CIM profile in CIM16.
Preparation of test cases is always a challenge that we need to face.
2) Issues discussion
· PetersenCoil
o the class will be marked as ShortCirciut
o all attributes will be required except offsetCurrent and positionCurrent
· GroundingImpedance
o the class will be marked as ShortCirciut
o x is required
· EarthFaultCompensator
o class will be marked as ShortCirciut
· association between DCPole and DCPoleAC will be added in the profile as in WG13
· association DCTerminal-DCnode should be required
· the .name in the DCTerminal should be optional
· Association InitialReactiveCapabilityCurve between DCPoleVSC and VSCCapabilityCurve is specified as bi-directional in the profile. The following should be kept in the profile:
DCPoleVSC [1..1]InitiallyUsedByDCPoleVSC
DCPoleVSC [1..1] DCPoleVSC
3) Action items
· CIMcontextor issue - in the Dynamics package (HTML version) concrete and abstract classes are mixed. This should be corrected to be like other profiles
· Check if gains in the standard models should be in PU
· Chavdar to produce the next version of the profile before 21 May
Participants
|
1
|
Frazzetta, Dario C…
|
2
|
Bozukov, Georgi
|
3
|
Zhu, Jun
|
4
|
nordanlycke, ingem…
|
5
|
Demaree, Kendall
|
6
|
Wiernowolski, Mich…
|
7
|
falk, herb
|
8
|
Olsen, Svein
|
9
|
Martinovic, Lajos
|
10
|
McMorran, Alan
|
11
|
Lopez, Rafael
|
12
|
Milin, Emilie
|
13
|
Zivkovic, Nemanja
|
14
|
Ford, Michael
|